Analysis of the breakdown in single-chamber circuit breaker

Show full item record

Files in this item

PDF CFM2007-0049.pdf 380.0Kb

Pour citer ce document :
URI: http://hdl.handle.net/2042/16667
Title: Analysis of the breakdown in single-chamber circuit breaker
Author: BOUSOLTANE , Karim; Guilherme Linhares; Pierre Chevrier; Georges Gaudart
Abstract: A hydrodynamic model for electrical arc modelling was used to develop a 420 kV 50 kA single-chamber circuit breaker. Normally, in order to estimate the gas breakdown probabilities, calculations based on gas density and the electric field are used. A second approach involves the use of energy equations to determine the re-strike possibility trough the creation of a leader channel. Leader parameters and more accurate predictions are obtained by comparing the experimental results and the leader calculations. However, these criteria assume a re-strike in pur gas, which is not true after introduction of the self blast volume.
Subject: S25 Phénomènes couplés et interfaciaux; leader; arc electrique; reclaquage
Publisher: AFM, Maison de la Mécanique, 39/41 rue Louis Blanc - 92400 Courbevoie