| Pour citer ce document : |
|
URI:
|
http://hdl.handle.net/2042/16667
|
|
Title:
|
Analysis of the breakdown in single-chamber circuit breaker |
|
Author:
|
BOUSOLTANE , Karim; Guilherme Linhares; Pierre Chevrier; Georges Gaudart
|
|
Abstract:
|
A hydrodynamic model for electrical arc modelling was used to develop a 420 kV 50 kA single-chamber circuit breaker. Normally, in order to estimate the gas breakdown probabilities, calculations based on gas density and the electric field are used. A second approach involves the use of energy equations to determine the re-strike possibility trough the creation of a leader channel. Leader parameters and more accurate predictions are obtained by comparing the experimental results and the leader calculations. However, these criteria assume a re-strike in pur gas, which is not true after introduction of the self blast volume. |
|
Subject:
|
S25 Phénomènes couplés et interfaciaux; leader; arc electrique; reclaquage |
|
Publisher:
|
AFM, Maison de la Mécanique, 39/41 rue Louis Blanc - 92400 Courbevoie |
|
Date:
|
2007-08-31 |